Just nu går det inte att komma åt Kokaihop.se. Detta på grund av ett strömavbrott i Amazons datacenter som påverkar förbindelsen till våra servrar. De arbetar på problemet och räknar med att allt skall vara igång igen inom 30-60 minuter. Störningen påverkar även medlemsfunktioner, receptuppdateringar och bilder i vår iPhone-app.
Mer information (klicka på Europe)
Uppdatering:
3:01 PM PDT A quick update on what we know so far about the event. What we have is preliminary, but we want to share it with you. We understand at this point that a lighting strike hit a transformer from a utility provider to one of our Availability Zones in Dublin, sparking an explosion and fire. Normally, upon dropping the utility power provided by the transformer, electrical load would be seamlessly picked up by backup generators. The transient electric deviation caused by the explosion was large enough that it propagated to a portion of the phase control system that synchronizes the backup generator plant, disabling some of them. Power sources must be phase-synchronized before they can be brought online to load. Bringing these generators online required manual synchronization. We’ve now restored power to the Availability Zone and are bringing EC2 instances up. We’ll be carefully reviewing the isolation that exists between the control system and other components. The event began at 10:41 AM PDT with instances beginning to recover at 1:47 PM PDT.